Flex-JZ POWER can be installed in all electrical systems in dry and damp interiors, especially in industrial environments, and can also be used outside; underwater installation is not permitted. Not suitable for constant moving. It is suitable as measuring, monitoring and control cable in the machine tool and plant engineering, in heat and air conditioning systems and refrigeration plants, etc.
Special features:
Flex-JZ POWER black is to a large extent resistant against oil and chemicals, rough but extremly flexible. All cables with three cores or more are included the green/yellow conductor arranged in the outer layer. Numbering distance approx. 20 – 50 mm. To avoid mistakes all numbers have a basic line.
CONSTRUCTION:
Fine strands of bare copper conductor
Stranding acc. to VDE 0295, class 5
Black cores with white numbers
JZ = earth conductor green/yellow in outer layer
OZ = without earth conductor
Outer sheath of special PVC, fire and oil resistant, resistant of UV – radiation
Sheath colour: black RAL 9005
TECHNICAL DATA:
Conductor Material
Copper, bare
Conductor class
Class 5
Core insulation
Special PVC
Core identification
DIN VDE 0293: Black cores with white numerals
Stranding
Cores twisted in layers
Outer sheath
Special PVC
Sheath colour
Black RAL 9005Rated voltage [V]: 600 / 1000
Testing voltage [V]
4000
Conductor resistance
20 MΩ x km
Current carrying capacity
DIN VDE (see technical guidelines)
Min. bending radius fixed [xd]
4 x d
Min. bending radius moved [xd]
15 x d
Working temp fixed min/max [C]
-40°C up to +80°C
Working temp moved min/mac [C]
-15°C up to +70°C
Temp at conductor max.
+ 70°C in operation, +160°C in case of short-circuit
Burning behaviour
VDE 0482-332-1-2/IEC 60332-1: flame-retardant and selfextinguishing